Deactivated Stage
Every now and then a service changes
to lower pressure ratios and requires fewer stages of compression on existing
equipment. Deactivating
a stage can be accomplished with allowing blowthru or by physically deactivating
a stage. Deactivated
stage methods are not to be confused with deactivating a cylinder within
a multi cylinder stage (see Deactivated Cylinder below).
Blowthru occurs when the compression
ratio across the compressor is not high enough to accommodate compression
in all the available stages. The
gas is compressed to full discharge pressure in the first several stages
and physically blows thru the last stage without further compression.
This blowthru
gas flow holds the suction and discharge valves open. If
the unit is close to allowing full compression on the last stage the valves
can flutter during this blowthru condition. Blowthru
is acceptable if the unit will not operate at extended periods of time
at this condition.
If the unit will operate at this
lower ratio for extended periods a stage of compression can be deactivated,
or taken out of service. For
shorter durations the cylinder can be deactivated by removing the suction
valves from both ends of the cylinders on the deactivated stage. For
longer periods the stage can be deactivated by removing all valves, removing
the piston and rod, rerouting the cylinder and packing lubrication to
the frame, replacing the packing with a solid plug and rebalancing the
reciprocating weights.
Any changes in operating conditions
warrants a review of performance to ensure proper operation within allowable
limits is maintained. Changes
in conditions
requiring deactivating a stage can have impacts to rod reversal, rod loads,
discharge pressure versus MAWP and potentially torsional responses.
These "extended periods of
time" should be defined by the user based upon frequency of re-activating
the stage, acceptable maintenance and the availability of manpower to
change the unit configuration. In
general, blowthru can be tolerated for days to a few weeks. Deactivating
by pulling the suction valves can be tolerated for months. Deactivating
by removing the piston and rod can be used for longer durations in the
terms of half a year and up. The
duration of deactivation by the blowthru and pulling suction valves are
discussed due to the likelihood of higher maintenance if the durations
are longer. Blowthru
conditions can cause the valves to open and close, without preferable
dynamics, resulting in possible broken valves before the next loading
of the stage. Pulling
the suction valves and leaving the piston and discharge valves in place
can also result in failure of the discharge valves over time and will
result in continued wear of the piston rings, wearbands and packing sealing
rings.
Deactivated Cylinder
Deactivating a cylinder that is
part of a stage is handled differently than deactivating an entire stage.
An example
would be if there are two first stage cylinders and typical unloading
methods are not enough, one first stage cylinder can be deactivated while
the other first stage cylinder continues to compress. If
an entire cylinder within a stage needs to be deactivated, this can be
done in one of two ways; Removal of the piston and rod, or non-acting
the cylinder.
Removal of the piston and rod
is the preferred
method to deactivate
a cylinder. This
is accomplished by removing the piston and rod, installing blank flange
blinds between the cylinder and pulsation vessels (suction and discharge),
installing a plug in place of the packing case, rebalancing and removing
the cylinder lubrication from the deactivated cylinder. Removing
the suction valves from both ends of the cylinder can be done rather than
installing flange blinds.
An entire single cylinder, when
part of a multiple cylinder stage using a manifolded suction pulsation
vessel, can be deactivated
by removing the suction valves from both ends of the cylinder. This
method is not
recommended by Ariel,
but has been performed successfully on specific installations. If
this method is successful, it can save down time for shorter term deactivation.
In this
method, the gas will be recycled from head end to crank end through the
suction gas passages and will heat up. In
most cases, the heat generated will be greater than the maximum allowable
average cylinder temperature of 285 F (140 C). If
this methods is used, cylinder temperature measurements must be taken
at the suction gas passages. The
discharge temperature measurement location will not read the cylinder
gas temperature.
Non-Acting Cylinders
A non-acting cylinder is a cylinder
that is installed, but is not compressing gas. There
are several ways a cylinder would be non-acting.
Blowthru
All Valves Removed
Suction Valves Removed
Piston and Rod Removed
Blank Throw
Non-Acting for Startup
Blowthru occurs when the compression ratio
across the compressor is not high enough to accommodate compression in
all the available stages. The
gas is compressed to full discharge pressure in the first several stages
and physically blows thru the last stage without further compression.
This blowthru
gas flow holds the suction and discharge valves open. If
the unit is close to allowing full compression on the last stage the valves
can flutter during this blowthru condition. Blowthru
is acceptable for short durations. Longer
durations can lead to premature valve failure in the stage with blowthru.
All
of the cylinder valves can be removed
if a stage of compression will need to be disabled for an extended period
of time. This
allows a larger flow area for the gas to pass through the cylinder valve
ports, reducing the pressure losses in the stage. This
also removes the valves from the wear life equation. Removing
all of the cylinder valves must be limited to deactivating an entire stage,
not just one cylinder of a mutli-cylinder stage.
Suction
valves can be removed
from a cylinder to disable a stage for much shorter periods. Some
of the benefits of lower pressure loss are attained, while having a shorter
downtime to remove valves.
Suction
valves can be removed
if a single cylinder of a mutli-cylinder stage needs to be disabled. Though
this method is not recommended by Ariel, it may be possible to non-act
a single cylinder within a stage. In
most cases, non-acting a cylinder within a stage will result in overheating
the cylinder beyond the capabilities of the non-metallic components within
the cylinder. If
this method is to be used for non-acting a cylinder within a stage, the
cylinder nozzle temperatures on the suction side (since suction valves
are removed) must be closely monitored so as not to exceed 285 F (140
C). This
method has been known to work in some specific circumstances, while in
the greater majority is not successful. The
cylinder to be non-acting must be part of a manifolded suction vessel
with the other cylinder(s) active.
Removal
of the piston and rod
to disable a stage can be done when the unit will operate with a disabled
stage for extended periods of time. Removal
of the piston and rod allows the wearing components to be removed and
the cylinder lubrication to be shutdown for the cylinder. This
is accomplished by removing the piston and rod, installing blank flange
blinds between the cylinder and pulsation vessels (suction and discharge),
installing a plug in place of the packing case, rebalancing and removing
the cylinder lubrication from the deactivated cylinder. Removing
the suction valves from both ends of the cylinder can be done rather than
installing flange blinds. The
definition of "extended period" is determined by the end user
and is a balanced of the time and equipment it takes to accomplish the
removal of the piston and rod against the savings for wear parts and lubrication.
Removal
of the piston and rod
is the preferred
method to non-act
a cylinder within a stage.
Blank
throws are locations
on the frame that can accommodate a cylinder, but are not mounted with
cylinders, ie., placing three cylinders on a four throw compressor. There
are two different balancing configurations for a blank throw, an active
crosshead guide and a balancing crosshead guide. An
active crosshead guide is a guide that can accommodate the mounting of
a cylinder and has standard crossheads and balance nuts installed. A
balancing crosshead guide, also referred to as a dummy guide, is a special
guide with added length to accommodate larger, special, balancing crossheads.
Cylinders
cannot be mounted on balancing guides. When
applying a blank throw, the reciprocating weight is not offset by gas
loads from compression. Therefore,
the weight of the blank throw should be minimized by mounting the smaller
of the cylinders on the opposing throw.
Cylinders can be non-acting
for start up purposes.
When the
available starting torque is not available for a fully bypassed compressor
start, unloading ends of the cylinders will help reduce some of the starting
torque. This
will require the use of suction valve unloaders or head end bypass devices.
Actuating
suction valve unloaders on the head end can help reduce the staring torque.
In some
cases, the motor inrush current must be further limited; suction valve
unloaders can be applied to both the head end and crank end to further
reduce the starting torque. When
both ends are non-acting for start up, a time limit of five (5) minutes
should be applied for the non-acting duration.
Ariel
Corporation Application Manual
7 August 2008